EPA Approves PMAA’s Low Liquid Level Alternative Test Method for Sumps

May 12, 2017 •

The U.S. Environmental Protection Agency’s (EPA’s) Office of Underground Storage Tanks (OUST) announced this week that it has approved the Petroleum Marketers Association of America’s (PMAA’s) low liquid level integrity test as an alternative method for containment sump testing that is required under the 2015 federal UST regulations.

 

The 2015 regulations require liquid testing every three years of all containment sumps used for interstitial monitoring of piping. However, the test method cited in the rule requires filling sumps with water above the penetration points in the sump wall. This sump test method would be prohibitively expensive for tank owners. Instead, the PMAA UST Task Force developed an alternative test for containment sumps.

 

The alternative requires filling sumps only to the level of a liquid sensing device equipped with a positive shutdown that is mounted below penetration points in the sump wall. PMAA’s alternative test method will significantly reduce reoccurring sump testing compliance costs for tank owners while being equally protective of the environment as filling the sump to the top, according to the OUST. This is an important victory for petroleum marketers that builds on previous cost-saving flexibility won by the PMAA UST Task Force during the rulemaking process.

 

OUST also clarified, at PMAA’s request, that water used for spill bucket and sump testing may be reused by third-party vendors at other sites to further reduce the cost of handling and disposal of test liquids. In addition, OUST clarified that if double-walled pipe systems using sumps for interstitial monitoring were installed before the date secondary containment for piping was first required by regulation, the tank owner may instead use leak detectors and annual line tightness testing to meet leak detection requirements. This would remove the need to test containment sumps, because annual line tightness tests would replace interstitial monitoring as the selected method of leak detection. OUST also approved PMAA’s request to allow the use of a liquid level audible alarm as a primary method of overfill protection where removing a fully functional in-tank probe to meet visual inspection requirements would destroy operability of the probe.

 

PMAA is continuing to work with OUST on additional flexibility measures for compliance with the 2015 UST requirements.

 